back
Chamber: Single
More suitable alternative: NO
Produces heat: NO
Produces Static: NO
Low Flash point: YES
Risk of Fire and Explosion - Probability: 1 x Exposure: 4 x Consequence: 3 = Risk Score: 12
Produces Fuel: YES
Risk of Fire and Explosion - Probability: 3 x Exposure: 4 x Consequence: 3 = Risk Score: 36
Per MSDS for activated charcoal: As with most organic solids, fire is possible at elevated temperatures or by contact with an ignition source. Activated carbon is difficult to ignite and tends to burn slowly (smolder) without producing smoke or flame. Wet activated carbon depletes oxygen from the air. Materials allowed to smolder for long periods in enclosed spaces, may produce amounts of carbon monoxide which may reach the lower explosive limit for carbon monoxide of 12.5% in air.
Produces Adverse: NO
Produces Mechanical: NO
See table below to understand risk level corresponding to each risk score.
Risk Score Risk Level Risk Description
> 100 5 Extremely dangerous: do not operate facility
50 - 100 4 Very high: stop use of equipment, processs or procedure
20 - 50 3 High: required urgent attention; proceed with care
5 - 20 2 Medium: attention needed but operation may continue
< 5 1 Low: acceptable risk but noted
* Burman F. Risk Assessment Guide for Installation and Operation of Clinical Hyperbaric Facilities. San Antonio, Texas: International ATMO; 6th Edition, 2019. ISBN: 978-0-578-22098-7

Created 7/17/2024 1:20:59 PM by lauren johnston   activated carbon msds.pdf